2.4 Downloading Test Records
1. Scroll to the "PRESS FOR DOWNLOAD" screen.
2. Connect the Tester to the Personal Computer.
Figure 5 - Tester Setup
3. Open Microsoft® HyperTerminal® or equivalent.
Configure the Serial COM Port as follows:
Set Baud Rate to 9600
Set Bits to 8
Set Parity to None
Set Stop Bits to 1
4. Press to initiate downloading.
5. When downloading is complete, a beep will be sounded and you will
be prompted to delete the tester records.
6. Save File - The saved file can be exported to another program such as
Microsoft® Excel®. See Program User Manual or Help File.