Section 4 – Programming Descriptions
11
Section [005] System Times
After entering Section [005], enter the 2-digit subsection number for the desired partition and program the Entry Delay 1, Entry Delay 2
and Exit Delay for each active partition on the system. Valid entries are from [001] to [255] or [045] to [255] for SIA CP-01 panels (in sec-
onds). Enter subsection [09] to program the Bell Cut-Off Time. Valid entries are from [001] to [255] (in minutes).
Section [006] Installer Code
The default Installer Code is [5555] or [555555] if 6-Digit Access Codes is enabled.
Section [007] Master Code
The default Master Code is [1234] or [123456] if 6-digit Access Codes is enabled.
Section [008] Maintenance Code
The default Maintenance Code is [AAAA] (not programmed). This code can arm any partition but cannot disarm unless the partition is in
alarm.
Section [009] to [011] PGM Outputs
The PC1616 and PC1832 have two on-board PGM outputs (PGM1 and PGM2). The PC1864 has four on-board PGM outputs (PGM1 to
PGM4). The panel has the capacity for up to 14 PGM outputs (8 additional low-current PGM outputs with PC5208 module, 4 additional
high-current PGM outputs with a PC5204 module).
PGM Output Options:
[37]
Night Zone: Functions like Interior Stay/Away but will remain bypassed if the user presses [
][1] to re-activate Stay/Away zones
when armed in the Stay mode
[87] Delayed 24-Hour Fire (Wireless): Same as Delayed 24-Hour Fire (Hardwire) but must be used for wireless smoke detectors
[88] Standard 24-Hour Fire (Wireless): Same as Standard 24-Hour Fire (Hardwire) but must be used for wireless smoke detectors
Option Description
[00] For Future Use
[01] Fire and Burglary: Output will activate (steady for burglary, pulsing for fire) if an alarm occurs on the selected partition
[02] For Future Use
[03] Sensor Reset: Output will normally be active and deactivate for 5 seconds when a [][7][2] fire reset command is entered or when an Auto-
Verify Fire alarm is detected
[04] 2-Wire Smoke: Configures PGM2 as 2-wire smoke detector input (PGM2 only)
[05] Armed Status: Output will activate when all of the selected partitions are armed
[06] Ready Status: Output will activate when all the selected partitions are in the Ready state (Ready light ON)
[07] Keypad Buzzer Follow: Output will activate and follow the keypad buzzer for the selected partition when the following events occur; entry
delay, door chime, audible exit delay, automatic arming pre-alert, 24-Hour Supervisory Buzzer zone alarm
[08] Courtesy Pulse: Output will activate during entry/exit delay if the selected partition is armed – will remain active for an additional 2
minutes after the entry or exit delay expires
[09] System Trouble: Output will activate when any selected trouble condition is present
[10] Latched System Event (Strobe): Output will activate when a selected condition occurs on any selected partition. Note output can be
programmed to follow timer
[11] System Tamper: Output will activate when any tamper condition is present
[12] TLM and Alarm: Output will activate if a telephone line trouble is present and then an alarm occurs
[13] Kissoff: Output will activate for 2 seconds when a valid kissoff is received from the central station
[14] Ground Start: Output will activate for 2 seconds when the panel attempts to seize the phone line (additional dial tone search must be
programmed in the central station phone number – HEX [D])
[15] Remote Operation: Output can be activated/deactivated via the DLS software
[16] For Future Use
[17] Away Armed Status: Activates when all of the selected partitions are armed in Away mode
[18] Stay Armed Status: Activates when all of the selected partitions are armed in Stay mode
[19] Command Output 1:Activates when a [][7][1] command is entered on the selected partition – Command can be programmed to require a
valid access code and output can be programmed to activate for the time programmed in Section [170] or programmed to latch.