HOOKUP DIAGRAM
37
NOTES
Security detection devices that require
power from the control panel must be
UL listed for the intended application
and operate over the range of 10.0 to
14.0 VDC. The DSC BRAVO Series is
a recommended UL listed motion
detector.
All voltage outputs are rated 11VDC
unregulated.
Refer to this manual for detailed
instructions on keypad wiring.
BATTERY
12V 4.0Ah
GELL-CELL
MAX battery charge
current is 360 mA.
Battery capacity for
emergency is at least
4 hours. Example:
Yuasa NP4-12.
BELL / SIREN
700 mA MAX
50 mA MAX
RED
BLK
YEL
GRN
PC2550RK Keypad
(3 MAX)
AUXILIARY
SUPPLY
OUTPUTS
400 mA MAX
T-1
R-1
TIP
RNG
GND
NO
AUX
BRN
GRY
GRN
RED
EEPROM RESET
RJ31X
UL LISTED
120 V 60Hz
Do not connect transformer
to receptacle controlled by a
switch. The transformer
must be UL listed and have a
restraining means.
AC
AUX
GND
SW
AUX
BELL
RED
BLK
Nut
Washer
Cabinet
Bolt
Ground
Rod
+11V
+11V
SWITCHED
- AUX
TRANSFORMER
16.5 VAC 40 VA
AUX
1AMP
BATT
5AMP
BELL
5AMP
GROUND START
CIRCUIT
BLK RED
WHT
PGM +AUX
RNG
GRN
RM-1
NC NO
YEL GRN
BLK RED
WHT
PGM OUTPUT RELAY
(Keypad [✱], [7])
COM
PGM +AUX
RM-1
TYPICAL BURGLARY
ZONE CONNECTIONS
NC
NO
End-Of-Line Resistors:
1KΩ 1/2 Watt
Normally Closed
contacts
Normally Open
contacts
Incorrect connections may result in
blown fuses or improper operation.
Check wiring before applying power.
4-wire Smoke
Detector Power
11 VDC
Alarm Initiating Loop
Resistance 100Ω MAX
RED
BLK
WHT
GRN
UL LISTED
4-wire Smoke Detector
End-Of-Line Resistor
EOLR-1
It is mandatory to use one UL listed indoor alarm
signaling appliance with minimum 85dB rating and a
current rating of 700 mA or less. Example: Wheelock
model 34T-12-R.
NOTE: Smoke detector must be latching type
(Example: ESL model 445C)
To reset smoke detectors - press [✱]
then hold down key [4] for 2-3 sec.
* Not allowed for UL Installations.
Bell Loop 700 mA MAX
BELL
Smoke Detector Power
Supervision Relay (DSC RM-1)
12V
DC 35mA
SW
AUX
BELL
FIRE
AUX
GND
TYPICAL FIRE ALARM
ZONE CONNECTIONS
In Out
In Out
Alarm
Contact
Temperature Range:
0°C-49°C(32°F-120°F)
Maximum Humidity: 85% R.H.
WARNING
1. Refer to instruction manual 29000124 for complete operating instructions.
2. The PC2550 is UL listed for limited energy installations per NEC article 760.
Recognized limited energy cable should be used. Observe NEC wiring
requirements and local codes as defined by the authority having jurisdiction.
Control Panel is suitable for the following
UL installations:
●
Household Fire and Grade A Household
Burglary
●
Grade A Local
●
Grade B Central Station and Grade A
Police Connect with basic line security
●
Grade C Central Station and Grade A
Poice Connect with basic line security
●
Refer to this manual
3. This equipment should be installed in accordance with National Fire
Protection Association Standard #74 (N.F.P.A. Batterymarch Park, Quincy
MA. 02269)
4. Do not replace fuses with a higher value than shown on this drawing.
Example: Basler Electric
BE 116240CAA-0002