[350] Communicator Format Options
Default: 04 SIA FSK I________I________I SIA -FSK is the approved format for Commercial Fire Applications.
NOTE: Do not change the communication format from its default setting.
[351] - [376] Communicator Call Direction Option 5 Alternate Communicator Option
NOTE: Not to be used for Commercial Fire applications
[377] Communication Variables
Default: O30 I________I________I________I AC Failure Communication Delay
For 24hr standby battery configuration enter any value between 006 and 012 hours (for a 60Hr standby battery configuration enter
any value from 015 and 030 Hours).
This battery depletion range is based on the AC trouble communication delay when the back up battery capacity is at least 25%
depleted but not more than 50 % of the proposed duration period. In this case either 24 hours or 60 hours of continuos backup)
Default: O30
I________I________I________I Test Transmission cycle (Land Line)*
*For Commercial Fire applications, 001 must be programmed for 1 day (24hours).
[382] Third Communicator Option Code
Default Option ON OFF
OFF
I________I________I________I 6 AC Transmission Delay in Hours AC Transmission Delay In Minutes
[378] Test Transmission Time of Day
NOTE: For Commercial Fire applications do not enter 9999 to disable this feature. A valid time of day must be entered
[390] -[393] - LINKS 1000 Preambles
NOTE: Do not use this section for Commercial Fire applications.
[401]-[406],[490],[499] Downloading Options
NOTE: NOT for field use. Must not be used for Commercial Fire applications
[501]-[504] Programmable Output Attributes.
Commercial Fire applications attributes from Sections [501] to [504] apply to the PGM outputs from the control panel only.
[701] - [703] International Programming
NOTE: These options must not be changed from the factory default settings for Commercial Fire applications
[801] - [806] Module Programming
NOTE: These sections are not to be used in Commercial Fire Applications.
[901] - Walk Test
NOTE: This is a diagnostic tool that is to be used by installers only.
[902] - [903] Module Field Supervision Reset/Field
NOTE: This is a diagnostic tool that is to be used by Installers only.
[904],[906],[993],[995]
NOTE: These sections are not to be used for Commercial Fire applications.
[999] PC5020 Factory Default Programming
This is a diagnostic tool that is to be used by Installers only if needed.
* If the system is defaulted, program the system according to the Commercial Fire Programming Guide for Central or Remote Sta-
tion Fire Monitoring, see Section 6 of the Installation Manual.