G E T T I N G S T A R T E D
7
2.3 Wire Routing for Power & Non-Power Limited
All wiring entry points are designated by the arrows. All circuits are classified UL installation power limited except for
the battery leads which are not power limited. A minimum ¼” (6.4mm) separation must be maintained at all points
between power limited and non-power limited wiring and connections.
Wire entry for power limited wiring must be separated by a different entry access from non-power
limited wiring.
2.4 Keybus Operation and Wiring
The Keybus is used by the panel to communicate with all modules
connected and by the modules to talk to the panel. The RED and BLK
terminals are used to provide power while YEL and GRN are clock
and data.
The 4 Keybus terminals of the panel must be connected to the 4
Keybus terminals or wires of all modules.
The following conditions apply:
Keybus should be run in minimum 22 gauge quad (0.5mm), two pair
twist preferred
the modules can be home run to the panel, connected in series or
can be T-tapped
any module can be connected anywhere along the Keybus, you do
not need a separate Keybus wire run for keypads, zone expanders
etc.
no module can be more than 1,000'/305m (in wire length) from the
panel
shielded wire is not necessary unless wires are run in an area that
may present excessive RF noise or interference
Example of Keybus Wiring
B
C
A
PANEL
500’
500’
150’
150’
B
C
A
PANEL
500’
500’
150’
150’
NOTENOTE
NOTENOTE
NOTE: Module (A) is wired correctly as it is within 1,000'/305m of the panel, in
wire distance.
Module (B) is wired correctly as it is within 1,000'/305m of the panel, in
wire distance
Module (C) is NOT wired correctly as it is further than 1,000'/305m
from the panel, in wire distance.
2.5 Current Ratings - Modules and Accessories
In order for the Power 832 system to operate properly, the power output capabilities of the main control and
expansion devices must not be exceeded. Use the data presented below to ensure that no part of the system is
overloaded and cannot function properly.
System Outputs (all 12 V
DC)
PC5010 VAUX: 500 mA. Includes one keypad. Subtract for each additional keypad, expansion module
and accessory connected to VAUX or Keybus.
BELL: 700 mA. Continuous Rating.
3.0 A. Short Term. Available only with standby battery connected.
PC5200/PC5204 VAUX: 1.0 A. Continuous Rating. Subtract for each device connected (max. load for burglary
applications).
3.0 A. Short Term. Available only with standby battery connected.
PC5208 VAUX: 250 mA. Subtract for each device connected. Subtract the total load on this terminal
from the PC5010 VAUX/Keybus output.
PC5100 VAUX: 100 mA. Subtract for each device connected. Subtract the total load on this terminal
from the PC5010 VAUX/Keybus output.
PC5108 VAUX: 100 mA. Subtract for each device connected. Subtract the total load on this terminal
from the PC5010 VAUX/Keybus output.
• PC5200 AUX: 1.0A max. (continuous). Subtract for each device connected. This rating applies for burglary
applications only.
PC5010 Device Ratings (@ 12 V
DC)
LCD5500 Keypad: 50 mA PC5208 Output Module: 50 mA
PC5508Z Keypad: 80 mA PC5132 Wireless Module: 125 mA
PC5516Z Keypad: 90 mA PC5100 Addressable Service Interface Module: 40 mA
PC5532Z Keypad: 120 mA Escort5580 Module: 150 mA
LCD5500Z Keypad: 85 mA PC5928 Audio Interface Module: 65 mA
PC5936 Module: 100mA PC5200 Power Supply: 20mA
PC5400 Printer Module: 65 mA PC5921 Intercom Audio Station: 20 mA
PC5921 EXT Door Box Audio Station: 20 mA LCD5501Z Keypad: 90mA
Keybus
NOTE: A minimum 1/4" (6.4mm) separation
must be maintained at all points between
power limited and non-power limited wiring
and connections.