DSC Power832 PC5O15 Manual de instalación Pagina 35

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 48
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 34
P R O G R A M D E S C R I P T I O N S
32
PGM Output Attributes ............................................ Section [141]-[142]
PC5208 Attributes .................................................. Section [143]-[150]
PC5204 Attributes .................................................. Section [151]-[154]
PGM Output timer ................................................... Section [164]
5.11 Telephone Line Monitor (TLM)
When the TLM Enable option is selected, the panel will supervise the phone line and will indicate a trouble
condition if the phone line is disconnected.
If the TLM Enable option is ON, the panel will check the telephone line every 10 seconds. If the telephone line
voltage is below 3V for the number of checks programmed in the TLM Trouble Delay section, the panel will report
a TLM trouble. The default number of checks is 3. Enter a number from [000] to [255] in the TLM Trouble Delay
section to change the number of checks before the TLM trouble is reported. Programming a delay means that a
momentary interruption of the phone line will not cause a trouble condition.
If the TLM Trouble Beeps When Armed option is enabled, the panel will indicate a TLM trouble at the keypad
while the system is armed. To activate the bell output in the case of a TLM trouble while the system is armed, the
TLM Audible (Bell) When Armed option must be selected.
When the trouble condition is restored, the panel can send a TLM Restoral reporting code. Any events which
occur while the phone line is down will also be communicated.
If the LINKS1000 Cellular Communicator, or an Alternate Communicator is being used, the panel can be
programmed to report a TLM Trouble Reporting Code.
TLM Enable/Disable ....................................................................................... Section [015], Option [7]
TLM Trouble Beeps When Armed or TLM Audible (Bell) When Armed ....... Section [015], Option [8]
TLM Trouble Reporting Code ......................................................................... Section [349]
TLM Restoral Reporting Code ....................................................................... Section [350]
TLM Trouble Delay .......................................................................................... Section [370]
5.12 Siren
The siren will silence after the number of minutes programmed for the Bell Cut-off time have passed.
The panel supervises the Bell output. If an open condition is detected, the panel will immediately indicate a
trouble condition by beeping the keypad twice every 10 seconds to alert the owner of the problem. The panel
can send a Bell Circuit Trouble and Trouble Restoral reporting codes to indicate the situation (see Section 5.8
Communicator Reporting Codes).
If the Temporal Three Fire Signal option is enabled, all Fire signals will follow the Temporal Three Pattern as
described in NFPA 72. If turned OFF all Fire signals will sound a one second on, one second off cadence.
If Fire Bell Continuous is enabled, the alarm output will sound until a code is entered. If disabled, the alarm will
sound until a code is entered or the bell cut-off time has expired.
Only firOnly fir
Only firOnly fir
Only fir
e zones will follow the Te zones will follow the T
e zones will follow the Te zones will follow the T
e zones will follow the T
emporal Thremporal Thr
emporal Thremporal Thr
emporal Thr
ee Firee Fir
ee Firee Fir
ee Fir
e Signal.e Signal.
e Signal.e Signal.
e Signal.
Bell Cut-off .............................................................. Section [005]
Bell Circuit Trouble Reporting Code ....................... Section [349]
Bell Circuit Trouble Restoral Reporting Code ........ Section [350]
Temporal Three Fire Signal Enable/Disable .......... Section [013], Option [8]
Fire Bell Continuous ............................................... Section [014], Option [8]
5.13 Test Transmission
To ensure that the communication link with the central station is functioning properly, the panel can be
programmed to send a test transmission signal on a regular basis.
The panel can send a Periodic Test Transmission Reporting Code at the programmed Test Transmission
Time of Day. The Test Transmission Cycle determines the period of time between tests. The option Land Line
Test Transmission in Minutes/Days allows you to select whether the Land Line Test Transmission cycle will be
counted in minutes or days. If you have selected the test transmission cycle to be in minutes, the Test
Transmission Time of Day counter will not apply.
The LINKS TThe LINKS T
The LINKS TThe LINKS T
The LINKS T
est Test T
est Test T
est T
ransmission can only be prransmission can only be pr
ransmission can only be prransmission can only be pr
ransmission can only be pr
ogrammed in days.ogrammed in days.
ogrammed in days.ogrammed in days.
ogrammed in days.
The TThe T
The TThe T
The T
est Test T
est Test T
est T
ransmission Cycle must be grransmission Cycle must be gr
ransmission Cycle must be grransmission Cycle must be gr
ransmission Cycle must be gr
eater than 10 minutes. A cycle timer of less than 10 minuteseater than 10 minutes. A cycle timer of less than 10 minutes
eater than 10 minutes. A cycle timer of less than 10 minuteseater than 10 minutes. A cycle timer of less than 10 minutes
eater than 10 minutes. A cycle timer of less than 10 minutes
will cause damage to the contrwill cause damage to the contr
will cause damage to the contrwill cause damage to the contr
will cause damage to the contr
ol panel.ol panel.
ol panel.ol panel.
ol panel.
When the test tranmission cycle is programmed, the panel will send a test transmission the following day. This will
indicate the beginning of the new test transmission cycle to central station.
The panel can also send a test for the LINKS1000 Cellular Communicator, if being used. If the LINKS1000 Test
Transmission Code is programmed, the panel will send a cellular test at the interval programmed in the LINKS
Test Transmission Cycle.
The end user can generate a communicator test. If the System Test Reporting Code is programmed, the panel
will send the signal when the System Test keypad command is entered (see Section 3.4 [
] Commands; []
[6] User Functions).