
41
[703] - Delay Between Dialing Attempts
For standard (force) dialing, the panel will go off-hook,
search for dial tone for 5 seconds, hang-up for 20 seconds,
go off-hook, search for dial tone for 5 seconds, then dial. If
there is no initial handshake recognized within 40 sec-
onds, the panel will hang up. This programmable timer
adds a delay before the next call is attempted, and is
defaulted to 001 for a total of six seconds.
5.10 Module Programming PWS Sect 10
The programming sections listed below pertain to addi-
tional modules on the system. For instructions on program-
ming these modules and a description of each programming
section, see the associated
Installation Manual
s.
1. PC5400 Programming Section [801]
2. PC5936 Programming Section [802]
• PC5936 audio interface will allow you to connect to 7
(with the PC4937 Audio Expansion Module 15) Interior
(PC5921) or exterior (PC5921EXT) Intercom Station.
These surface mounted stations contain a speaker and a
microphone. This module enables Page/Answer, Do
Not Disturb, Baby Monitor, Answer Incoming Calls,
Doorbell Function, and Background Music features in
your alarm. This module also has the Listen-in feature
for central station monitoring. The central station can
select the audio station, listen/talk, extend on-line time
and hang up. The Listen-In feature can be enabled sepa-
rately for telephone numbers 1/3 and 2.
All Talk/Listen
and/or video sessions will be disconnected if the panel
needs to communicate alarms to the central station.
• Alternate Communicator Programming Section [803]
• PC5132 Programming Section [804]
NOTE:
All Talk/Listen and/or video sessions are disconnected
when the panel communicates alarms to the central station.
• T-Link Programming Section [851]
NOTE:
Option [5] in Section [382] must be enabled to access
this section.
The T-Link module can be used to communicate panel
events in SIA format over a Local Area Network (LAN). It
can also be used for downloading (this requires DLS2002
and higher).
Telephone 1 & 3 Listen-In Enabled . . . . . . .Section [381], Option 5
Telephone 2 Listen-In Enabled. . . . . . . . . . .Section [381], Option 6
5.11 Special Installer Instructions PWS Sect 11
[901] - Installer Walk Test Mode Enable / Disable
The Installer Walk Test
Installer Walk Test Installer Walk Test
Installer Walk Test can be used to test the alarm state of
each zone of the panel. The Walk Test cannot be used to test
zone type [24]. Before beginning the Walk Test, ensure the
following conditions are met:
1. The panel is disarmed
2. The Keypad Blanking option is disabled (section [016]:
[3])
3. The Fire Bell is Continuous option is disabled (section
[014]: [8])
4. The Transmission Delay is disabled, if Transmission
Delay is not required (section [377])
NOTE:
Fire Troubles are not supported in Walk Test.
To perform a Walk Test, do the following:
1. Enter Installer Programming
2. Enter Section [901]
When any zone is violated the panel will activate the Bell
Output for two seconds and log the event to the event
buffer. Check the event buffer to ensure that all zones and
FAP keys are functioning properly.
NOTE:
If there is no zone activity on the system for 15 min-
utes, the system will end the Walk Test and return to the
normal state.
To stop the test, you must do the following:
1. Enter Installer Programming
2. Enter Section [901]
Zones do not have to be restored to stop the test. After the
test is complete, check the event buffer to ensure that the
Audible/Silent 24-Hr. PGM alarms have been restored.
NOTE:
The Alarm Memory is cleared upon entering Walk
Test mode. When the Walk Test is complete, the Alarm
Memory will indicate the zones tested. The Alarm Memory
will be cleared the next time the panel is armed.
NOTE:
While the Walk Test is in progress, all three LEDs
(Ready, Arm, Trouble) will flash at a rapid rate. At the start
of the Walk Test, a TS signal will be communicated. When
the test is stopped a TE (test end) is communicated.
[902] - Reset Module Supervision
All modules will automatically enroll within one minute
upon power up (except the PC5132 if there are no serial
numbers programmed). If modules are to be removed, this
section should be entered after the removal of the modules
so that it can clear any supervisory Troubles that may be
present. When this mode is entered, the system will re-eval-
uate the components of the system.
NOTE:
It may take up to a minute to enroll or delete a
module. Before entering Section [903] to view the module
field, this time should be taken into account.
If there is a module that is not properly communicating
with the system and this section is entered, the module
will be deleted from the system.
Once executed, all pending Supervisory Trouble Restorals
will not be logged or transmitted.
[903] - Module Supervision Field
When this mode is entered, the system will display all of
the modules presently enrolled on the system as indicated
below.
[904] - Module Placement Test
Module Selection
Module SelectionModule Selection
Module Selection
Upon entering Section [904], a 2-digit entry will be
required to select the zone number to be tested. Valid
entries are 01-32 for Zones 01-32 respectively. On an LCD
keypad, there are two ways to make a zone selection:
direct entry of 01-32, or by scrolling across to the descrip-
tion of the module (i.e. ’Zone 1’). If a module is selected
that is not enrolled, an error tone will sound.
[903] MODULE SUPERVISION FIELD
Indicator Module
Lights 1-8 Keypads 1-8
Lights 9-11 Zone Expander Groups 1-3
Light 15 For Future Use
Light 17 PC5132
Light 18 PC5208
Light 19 PC5204
Light 20 PC5400
Light 21 PC59XX
Light 22 Alternate Communicator (i.e. DVACS, Skyroute)
Light 23 For Future Use
Light 24 Escort5580(TC)
Light 25 For Future Use
Light 26-29 PC520X1-4
Comentarios a estos manuales