DSC PC5020 Manual de instalación Pagina 12

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 53
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 11
Installation and Wiring: 2.9 Removing Modules
7
In LED keypads, zone lights will be turned on according to what
modules the panel has found on the system. Refer to the follow-
ing chart:
Keypad Light Module/Device Present
[1] Keypad 1
[2] Keypad 2
[3] Keypad 3
[4] Keypad 4
[5] Keypad 5
[6] Keypad 6
[7] Keypad 7
[8] Keypad 8
[9] Zones 9 to 16
[10] Zones 17 to 24
[11] Zones 25 to 32
[12] Zones 33 to 40
[13] Zones 41 to 48
[14] Zones 49 to 56
[15] PC5100
[16] Zones 57 to 64
[17] PC5132
[18] PC5208
[19] PC5204
[20] PC5400
[21] PC5936
[22] LINKS2X50/Skyroute™
[23] DLM-4L v1.0
[24] Escort5580
[25] Future Use
[26] PC520X-1
[27] PC520X-2
[28] PC520X-3
[29] PC520X-4
If a module is connected but does not show as being present, it may
be due to any of the following reasons:
it is not connected to the Keybus
there is a Keybus wiring problem
the module is more than 1,000'/305m from the panel
the module does not have enough power
the PC5132 does not have any devices added
2.9 Removing Modules
If a module is no longer required on the system, the panel must be
told to stop supervising the module. To do this:
1. Remove the module from the Keybus.
2. Press [*] [8] [Installer Code] to enter Installer Programming.
3. Press [902] to enable supervision. The panel will automatically
search for all modules on the system, will see that the module
has been removed, and will stop supervising it.
4. Once the search is complete (it will take about 1 minute) enter
section [903] to confirm that the correct modules are supervised
on the system.
2.10 Zone Wiring
For a complete description of the operation of all zone types, see
section 5.3 Basic Programming PWS Sect 3 on page 17.
There are several different ways in which zones may be wired,
depending on which programming options have been selected. The
panel can be programmed to supervise normally closed, End of Line,
or Double End of Line loops. Refer to the following sections to study
each type of individually supervised zone wiring.
NOTE: Any zone programmed for Fire or 24 Hour Supervisory must
be wired with a single End of Line (EOL) resistor regardless of the
type of zone wiring supervision selected for the panel (section [013],
options [1] and [2]). See Zone Definitions [001] [004]. If you change
the zone supervision options from DEOL to EOL or from NC to DEOL
(section [013], options [1] or [2]), power the system down com-
pletely, and then power it back up for correct operation.
Normally Closed (NC) Loops
To enable normally closed loops, programming section [013], option
[1] must be ON.
NOTE: This option should only be selected if Normally Closed (NC)
devices/contacts are being used.
Normally Closed Loops. . . . . . . . . . . . . . . Section [013], Option [1]
Single End Of Line (EOL) Resistors
To enable panel detection of single end-of-line resistors, program-
ming section [013], options [1] and [2] must be OFF.
NOTE: This option should be selected if either Normally Closed
(NC) or Normally Open (NO) detection devices or contacts are being
used.
End of Line Resistors . . . . . . . . . . . . . . . . Section [013], Option [1]
Single End of Line Resistors . . . . . . . . . . . Section [013], Option [2]
Double End of Line (DEOL) Resistors
Double End of Line resistors allow the panel to determine if the zone is
in alarm, tampered or faulted.
To enable panel detection of double end of line resistors, program-
ming section [013], option [1] must be OFF and option [2] must be ON.
NOTE: If the Double EOL supervision option is enabled, all hard-
wired zones must be wired for Double EOL resistors, except for Fire
and 24 Hour Supervisory zones.
Do not wire DEOL resistors on keypad zones.
Do not use DEOL resistors for Fire zones or 24 Hour Supervisory
zones. Do not wire Fire zones to keypad zone terminals if the DEOL
supervision option is selected.
This option can only be selected if Normally Closed (NC) detection
devices or contacts are being used. Only one NC contact can be con-
nected to each zone.
The following chart shows zone status under certain conditions:
End-of-Line Resistors . . . . . . . . . . . . . . . . Section [013], Option [1]
Double End-of-Line Resistors . . . . . . . . . . Section [013], Option [2]
Loop Resistance Loop Status
0 (shorted wire, loop shorted) Fault
5600 (contact closed) Secure
Infinite (broken wire, loop open) Tamper
11200 (contact open) Violated
ANY Z
TERMINAL
ANY COM
TERMINAL
ANY Z
TERMINAL
ANY COM
TERMINAL
WWW.DIYALARMFORUM.COM
Vista de pagina 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 52 53

Comentarios a estos manuales

Sin comentarios