Programming Sections: 5.6 Communicator Programming PWS Sect6
29
Alarm Canceled: this reporting code will be sent if a valid access
code is entered during the Alarm Cancel window. If a valid access
code is entered during this window, then the Alarm Canceled event
is logged and sent. When the central station has acknowledged this
reporting code/event, a keypad ring-back will occur.
[329] - Priority Alarm and Restoral Reporting Codes
[F], [A], [P] Alarm: this reporting code will be sent if the [F] [A] or [P] key is
used to generate manual alarms.
Auxiliary Input Alarm: this reporting code will be sent when PGM2 is
being used for two wire smoke detectors and the 2-wire smoke detector goes
into alarm.
[F], [A], [P] Restoral: this reporting code will be sent after the [F] [A] [P]
alarm reporting code is sent.
Auxiliary Input Restore: the panel will transmit this reporting code when
the 2-wire smoke detector has restored after an alarm.
[330]-[333] - Tamper Reporting Codes, Zones 1-64
If the panel is programmed for Double EOL zones (See Section 2.10
"Zone Wiring") the panel will report a Zone Tamper Alarm Report-
ing Code if an open condition is present on a zone. A different
reporting code can be programmed for each zone for identification.
[334]-[337] - Tamper Reporting Codes, Zones 1-64
The Zone Tamper Restoral Reporting Code will be transmitted
immediately when the tamper condition is restored.
[338] - Miscellaneous Tamper Reporting Codes
General System Tamper: a General System Tamper Reporting Code
will be transmitted when the tamper zone on any module is violated.
General System Tamper Restoral: the General System Tamper
Restoral Reporting Code will be transmitted when the tamper zone
on the module is restored.
Keypad Lockout: the panel will transmit the Keypad Lockout
Reporting Code if the lockout is activated.
[339]-[340] - Closing (Arming) Reporting Codes, Zones
1-32
The panel will transmit a Closing Reporting Code to indicate a Parti-
tion(s) is armed. A different reporting code can be transmitted for
each User Code, Partition Master Code and System Master Code to
identify who armed the partition(s).
[341] - Miscellaneous Closing (Arming) Reporting
Codes
Closing by Duress Code 33/34: a Closing by Duress Code Report-
ing Code will be transmitted in addition to the Duress reporting code
if a Partition(s) is armed using a Duress Code
Closing by Master or Supervisory Code: the panel will transmit a
Closing Reporting Code to indicate a Partition(s) is armed. A different
reporting code can be transmitted for each User Code, Supervisory
Code and System Master Code to identify who armed the Parti-
tion(s).
Partial Closing: a Partial Closing Reporting Code will be transmitted
if a Partition is armed with zones manually bypassed. The code will
also be transmitted if a Partition Auto Arms with zone(s) in violation.
Special Closing: a Special Closing Reporting Code will be transmit-
ted if the Partition(s) is armed using any of the following methods:
• Quick Arm
• Auto Arm
• Arming via the DLS Software
• Arming via Keyswitch
• 'Away' Function Key Arming
• Arming with the Maintenance Code.
• 'Stay' Function Key arming
Late to Close: a Late to Close Reporting Code will be transmitted if
a partition isn't armed before the auto-arm start time when the late
to close option, (Section 017, option 5) is enabled.
[342]-[343] - Opening (Disarming) Reporting Codes
Access Codes 1-32
The panel will transmit an Opening Reporting Code to indicate
partition(s) is disarmed. A different reporting code can be transmit-
ted for each user code, partition master code and system master
code to identify who armed the partition(s).
[344] - Miscellaneous Opening (Disarming) Reporting
Codes
Opening by Duress Code 33/34: This Reporting Code will be trans-
mitted in addition to the duress reporting code if a Partition(s) is dis-
armed using a Duress Code
Opening by Master or Supervisory Code: The panel will transmit
this reporting code to indicate a Partition(s) is armed. A different report-
ing code can be transmitted for each User Code, Supervisory Code and
System Master Code to identify who armed the Partition(s).
Auto Arm Cancellation: This reporting code is transmitted when the
Auto Arming sequence is canceled or Postponed
Special Opening: A Special Opening Reporting Code will be transmit-
ted if the Partition(s) is disarmed using any of the following methods:
• Disarming using the Maintenance Code
• Disarming via the DLS Software
• Disarming via keyswitch
[345] - Maintenance Alarm Reporting Codes
Battery Trouble Alarm: the panel will transmit a Battery Trouble
Alarm Reporting Code when the backup battery drops below 11.5
V
DC.
AC Failure Trouble Alarm: the panel will transmit an AC Failure
Trouble Alarm Reporting Code when the AC to the panel is lost and
the AC Failure Communication Delay timer expires.
Bell Circuit Trouble Alarm: a Bell Circuit Trouble Alarm Reporting
Code will be transmitted immediately if an open condition is mea-
sured on the Bell Output of the main panel.
Fire Trouble Alarm: a Fire Trouble Alarm Reporting Code will be
transmitted immediately when an open condition is measured on
any Fire type zone.
Auxiliary Power Supply Trouble Alarm: the Auxiliary Power Sup-
ply Trouble Alarm Reporting Code will be transmitted if the AUX out-
put is shorted.
TLM Trouble: a TLM Trouble Reporting Code can only be transmit-
ted if a LINKS1000/2X50 Communicator is being used (See Section
5.26 "LINKS1000 Cellular Communicator"). The panel will only
transmit the signal after the time programmed for the TLM Trouble
Delay.
General System Trouble: a General System Trouble Reporting Code
will be transmitted if the panel detects any of the following:
• AC Power Failure
• Low Battery
• AUX Output Trouble
• Output #1 on the PC5200/PC5204 Power Supply/Output Module.
General System Supervisory Trouble: a General System Supervi-
sory Trouble Reporting Code will be transmitted if any module goes
missing from the Keybus. If the module is a zone expander the panel
will also transmit the Zone Expander Supervisory Alarm Trouble
Reporting Code.
[346] - Maintenance Alarm Reporting Codes
Battery Trouble Restoral: the Battery Trouble Restoral Reporting
Code will not be transmitted until the battery has been charged over
12.5 V
DC.
AC Failure Trouble Restoral: the AC Failure Trouble Restoral
Reporting Code will be transmitted once AC power has been
restored for the amount of time programmed for AC Failure Com-
munication delays.
Bell Circuit Trouble Restoral: the Bell Circuit Trouble Restoral
Reporting Code will be transmitted as soon as the open condition on
the bell output is corrected.
Fire Trouble Restoral: the Fire Trouble Restoral Reporting Code will
be transmitted when the correct resistance value is measured on any
Fire type zone.
Auxiliary Power Supply Trouble Restoral: the panel constantly
checks the AUX output, when the excessive current draw is removed
the panel will reset the output and transmit an Auxiliary Power Sup-
ply Trouble Restoral Reporting Code.
TLM Restoral: the TLM Restoral Reporting Code will be transmitted
immediately after the trouble is restored.