DSC PC5020 Manual de instalación Pagina 13

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 53
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 12
8
Fire Zone Wiring - 4-wire Smoke Detectors
All zones defined as Fire (see section 5.3 Basic Programming PWS
Sect 3 on page 17) must be wired according to the following dia-
gram:
For a complete description of how fire zones operate, see section 5.3
Basic Programming PWS Sect 3 on page 17.
Fire Zone Wiring - 2-wire Smoke Detectors
If PGM 2 has been programmed for 2-Wire Smoke Detector connec-
tion (see section 5.3 Basic Programming PWS Sect 3 on page 17) ,
the detectors must be wired according to the following diagram:
For a complete description of how fire zones operate, see section 5.3
Basic Programming PWS Sect 3 on page 17.
Keyswitch Zone Wiring
Zones may be programmed to be used as keyswitch arming zones
and must be wired according to the following diagram:
For a complete description of how keyswitch zones operate, see sec-
tion 5.3 Basic Programming PWS Sect 3 on page 17.
LINKS1000 Supervisory (24 Hour Supervisory)
When using the LINKS1000 cellular communicator, any main board
zone may be configured for LINKS1000 Supervision. Program this zone
as zone type (09), 24 Hour Supervisory in section [001].
With a 24 Hour Supervisory zone, if the LINKS1000 experiences a
trouble, the zone will be violated, causing the panel to report the
event to the central station. This type of zone always requires a single
EOL resistor (5600).Refer to Links 1000 Installation Manual wiring
diagram for installation.
LINKS1000 Answer
If the LINKS1000 cellular communicator is
being used a zone may be configured for
LINKS1000 Answer to allow downloading
to be performed in the event of telephone
line failure.
When the LINKS1000 receives a telephone
call it will activate the RING terminal on
the LINKS1000 circuit board. This terminal
can be used to violate a zone programmed as (24) LINKS1000
Answer (see section 5.3 Basic Programming PWS Sect 3 on page 17),
causing the panel to seize the telephone line and begin communica-
tion with the downloading computer.
The zone programmed as LINKS1000 Answer ALWAYS requires a sin-
gle EOL resistor (5600) and must be wired according to the dia-
gram above.
NOTE: The LINKS1000 Answer zone is only required for download-
ing to the panel via the LINKS1000, or for remotely connecting to
the Escort5580 module via the LINKS1000.
NOTE: When using the LINKS1000, Busy Tone Detection must not
be used.
NOTE: Keypad zones cannot be used for 24 Hour Supervisory or
LINKS1000 Answer.
LINKS 2X50/LINKS 3000/Skyroute™
Refer to the LINKSX50, LINKS3000 and Skyroute™ Installation Man-
uals for wiring and installation details.
2.11Keypad Zones
Keypads with zone inputs can be connected to devices such as door
contacts. This saves you from running wires back to the control panel
for every device.
To install the keypad, open the keypad plastic by removing the screw
at the bottom of the unit. Locate the five terminals on the keypad
circuit board. Connect the four Keybus wires from the control panel:
the red wire to R, the black to B, the yellow to Y and the green to G.
To connect the zone, run one wire to the Z terminal and the other to
B. For powered devices, use red and black to supply power to the
device. Run the red wire to the R (positive) terminal and the black
wire to the B (negative) terminal.
When using end of line supervision, connect the zone according to
one of the configurations outlined in Section 2.10 ”Zone Wiring” on
page 7.
NOTE: End of line resistors must be placed on the device end of the
loop, not at the keypad.
NOTE: Keypad zones do not support DEOL resistors.
Assigning Keypad Zones
When using keypad zone inputs, each input used must be assigned a
zone number in Installer’s Programming.
First, ensure that you have enrolled all installed keypads into the
desired slots (see section 2.7 Keypad Assignment on page 6).
Next, enter programming section [020] to assign the zones. There
are eight programming locations in this section, one for each keypad
slot. Enter a 2-digit zone number for each of the keypad zones. This
number must be entered in the location corresponding to the keypad
to which each zone is connected.
NOTE: If a keypad zone input is assigned on zone number from 1
to 8, the corresponding zone cannot be used on the main control
panel.
Once the keypad zones are assigned, you must also program zone
definitions and zone attributes (See Section 5.3 Basic Programming
PWS Sect 3 [001]-[004] and Section 5.4 Advanced System Program-
ming PWS Sect 4 [101]-[164])
WWW.DIYALARMFORUM.COM
Vista de pagina 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 52 53

Comentarios a estos manuales

Sin comentarios